We are offering Constant Voltage Transformer to our clients that is widely used in several industries to provide constant electrical power to the appliances. The voltage transformer is an electrical instrument that set up or step down the voltage level. Transformers work based on the Faraday's law of induction. Our offered Constant Voltage Transformer is a durable and very functional product. It is assembled using top grade electronic components, therefore, a long service life of the transformer is ensured.
FEATURES
In Hi-Rel CVT, the AC mains powers the input winding which is widely separated physically from the isolated output winding. The input winding normally runs at very moderate Flux linkage levels. The output winding exhibits an intrinsic energy characteristic and this energy storage operates in conjunction with mains capacitor to produce self-generated AC flux field which is indirectly excited from the input winding.
The result is instantaneous voltage regulation. No transient and spikes. Sinewave output. A perfect answer and remedy for every electronic equipment.
SALIENT FEATURES
No semiconductors or moving parts used, hence very high reliability
No feedback control used
Intrinsic current limiting and short circuit protection
Output voltage correction within ½ Cycle ( 10 ms) from no load to full load for specified load and line variation
Short term over load capability
Energy storage for line loss up to 3 ms at typical loads
Higher input voltage control range, for loads less than rated load
Very high line transient/spike rejection capability and excellent input to output isolation characteristics
Output floating (optional)
RANGE
Hi-Rel CVT is available in a wide range.. from 100VA to 5000 VA with load test conducted at unity power factor for all ratings.
FIELDS OF APPLICATION
Computers, Data Processing equipment, Colour Photography Labs., Bio-medical equipment, PA equipment, Telecommunication, TV, VCD/DVD recorders & players, Teleprinters, Fax machines and all other sensitive electronic devices.
SPECIFICATIONS
Input Voltage | 180V-260V (other choices on request) |
Line Frequency | 50Hz |
Output Voltage | 220/230± 1% |
Output Stepload response | 2 cycles (30 to 40 milliseconds) |
Efficiency | 90% (approx) under full load conditions |
Output Waveform | Sinusoidal |
Waveform Distortion | 5% (approx) under full load conditions |
Load Power Factor | 0.75% lag to 0.9% lead |
Ambient Temperature | -5ºC to 50ºC |
Transformer Type | Ferro-Resonant |
Effect of Frequency | 1.6% (approx) change in output voltage for every 1% change in |